FAP541 Digital fire detection control unit | 1 loop line / 2 open lines
Product Code: EK80SC61021
FAP541 Digital fire detection control unit | 1 loop line / 2 open lines
Brand: ElkronProduct Code: EK80SC61021
- 1 loop line (Class A) or 2 open lines (Class B)
- Ability to manage up to 128 devices per loop
- 4×40 characters backlit display
- Log file with 1000 event records
- 480 programmable zones, 240 zone groups, 240 device groups
- Possibility of creating a loop of at least 2km with shielded cable 2×1.5mm²
- Dimensions (W×H×D): 490×350×145 mm
- Certification EN54 2-4, No. 0051-CPD-0240
- 1 loop line (Class A) or 2 open lines (Class B)
- Ability to manage up to 128 devices per loop
- Automatic learning and rendering of logical address of the field devices
- 4×40 characters backlit display
- Log file with 1000 event records
- Display event history on screen
- 10 programmable passwords in 3 levels
- 480 programmable zones, 240 zone groups, 240 device groups
- USB port for local PC connection and programming via proprietary software
- Ability to monitor signal-to-noise ratio (SNR) level of detectors
- Built-in real-time clock with battery backup
- Non-volatile memory
- Panel relay outputs: alarm, siren, fault, programmable (mains failure / exception)
- Monitor the first 10 devices entering alarm status with digital time-voltage display
- Internal buzzer
- Single point / zone exception
- Power supply: 230Vac
- Maximum output current: 1.5A@24Vdc
- Charge limit and battery status check
- Battery capacity: 2×12A@12Vdc
- Possibility of creating a loop of at least 2km with shielded cable 2×1.5mm²
- Noise protection up to 30Vm
- Common communication protocol for all system control units
- Dimensions (W×H×D): 490×350×145 mm
- Certification EN54 2-4, No. 0051-CPD-0240